INTERACTIVE APPLICATION GUIDE |
(Current UL Approved Maximum damper sizes, width x height in inches) |
Consult Ruskin for solutions on application sizes larger than shown below. |
|
UL555 & UL555S Combination Fire And Smoke Rated Dampers (Multi-Blade Dynamic-Rated) |
Return to top |
Product Models |
Walls |
Floors |
One-Side Angle Installation |
"Out of
Wall/Floor" |
Grille Access in Shafts & Coridor Walls |
Round Duct |
Fire Stop
(no angles)
Installation |
"Tunnel" Corridor
Ceilings |
Roof/Floor
Ceiling
Assemblies |
Smoke Detector |
FSD60 / 1.5hr / Class 1 / AirFoil |
120x96 |
144x96 |
90x48 or 48x90 |
|
|
94 |
90x48 |
|
|
Yes |
FSD60LP / Low Profile / 1.5hr / Class 1 |
36x14 |
36x14 |
36x14 |
|
|
|
36x14 |
|
|
|
FSD60M - Modulating / Class 1 |
120x48 or 64x96 |
120x48 or 64x96 |
90x48 or 48x90 |
|
|
|
|
|
|
Yes |
FSD60-BAL / Balancing / 1.5 hr / Class I |
32x48 |
30x48 |
32x48 or 30x48 |
|
48x48 (FSD60FA-BL) |
|
|
|
|
C/F |
FSD60-2 /1.5hr / Class 2/ AirFoil |
120x96 |
144x96 |
90x48 or 48x90 |
|
|
94 |
90x48 |
|
|
Yes |
FSD60-V /1.5hr / Class2 / Vertical Blade / AirFoil |
48x32 |
48x32 |
48x32 |
|
36x32 (FSD60-VGA) |
30 |
48x32 |
|
|
Yes |
FSD60-3 / 3hr / Class 1 / AirFoil |
120x96 |
144x96 |
|
|
|
94 |
90x48 |
|
|
Yes |
FSD60-3M / 3hr / Modulating / Class I / Airfoil |
120x48 |
120x48 |
|
|
|
|
|
|
|
|
FSD60FA / 1.5hr / Class 1 / Front Access / AirFoil |
|
|
|
|
48x48 |
C/F |
|
|
|
C/F |
FSD36FA / 1.5hr / Class 2/ Front Access / 3V |
|
|
|
|
36x36 |
C/F |
|
|
|
C/F |
FSD "OW" / 1.5 hr Out of Wall/Floor |
|
|
|
36x36 |
36x32 (FSD60V-OW) |
34 |
|
|
|
Yes |
FSD "GA" / 1.5 hr. / Grille Access |
|
|
|
|
36x36 |
34 |
|
|
|
|
FSD37 / 1.5hr / Class1 / 3V Groove |
120x96 |
144x96 |
90x48 or 48x90 |
|
|
94 |
90x48 |
|
|
Yes |
FSD36 / 1.5hr / Class2 / 3V Groove |
126x96 or 72x122 |
144x96 |
90x48 or 48x90 |
|
|
94 |
90x48 |
|
|
Yes |
FSD35 / 1.5hr / Class3 / 3V Groove |
126x96 |
144x96 |
90x48 or 48x90 |
|
|
94 |
90x48 |
|
|
Yes |
FSD37SS / Stainless / 1.5hr / Class 1/ 3V |
90x32 |
90x32 |
90x32 |
|
|
|
|
|
|
|
FSD36SS / Stainless / 1.5hr / Class 2/ 3V |
90x48 |
90x48 |
90x48 |
|
|
|
|
|
|
|
FSD35SS / Stainless / 1.5hr / Class 3/ 3V |
90x48 |
|
90x48 |
|
|
|
|
|
|
|
FSDR25 / 1.5Hr / Class 1 / "True Round" |
24 |
24 |
24 |
|
|
24 |
|
|
|
C/F |
FSD60/36C / 1hr / Tunnel Corridor |
24x24 |
24x24 |
|
|
|
22 |
|
24x24 |
|
C/F |
DFSDR1 / 1hr / Tunnel Corridor |
|
|
|
|
|
12 |
|
12 |
|
C/F |
UL555S Smoke Dampers (Multi-Blade Dynamic-Rated) |
Return to top |
Product Models |
Walls |
Floors |
One-Side Angle Installation |
"Out of
Wall/Floor" |
Grille Access in Shafts |
Round Duct |
Fire Stop
(no angles)
Installation |
"Tunnel" Corridor
Ceilings |
Roof/Floor
Ceiling
Assemblies |
Smoke Detector |
SD60 / Class 1 / Airfoil Blades |
144x96, 288x48, or 72x144 |
144x96, 288x48, or 72x144 |
|
|
|
94 |
|
|
|
Yes |
SD60M / Modulating Class I / Airfiol Blades |
120x48 |
120x48 |
|
|
|
|
|
|
|
Yes |
SD60BAL / Balancing Class I / Airfoil Blades |
36x48 |
36x48 |
|
|
|
|
|
|
|
Yes |
SD60-2 / Class 2 / Airfoil Blades |
144x96, 288x48, or 72x144 |
144x96, 288x48, or 72x144 |
|
|
|
94 |
|
|
|
Yes |
SD50 / Class 1 / Aluminum Airfoil |
144x96, 288x48, or 72x144 |
144x96, 288x48, or 72x144 |
|
|
|
94 |
|
|
|
Yes |
SD37 / Class 1 / Airfoil or 3V |
144x96, 288x48, or 72x144 |
144x96, 288x48, or 72x144 |
|
|
|
94 |
|
|
|
Yes |
SD36 / Class 2 / 3V Blades |
144x96, 288x48, or 72x144 |
144x96, 288x48, or 72x144 |
|
|
|
94 |
|
|
|
Yes |
SD35 / Class 3 / 3V Blades |
144x96, 288x48, or 72x144 |
144x96, 288x48, or 72x144 |
|
|
|
94 |
|
|
|
Yes |
SDRS25 / Class 2 / True Round |
24 |
24 |
|
|
|
24 |
|
|
|
C/F |
SDRS25SS / Class 2 / True Round |
24 |
24 |
|
|
|
24 |
|
|
|
C/F |
UL555 Static "Fans Off" Fire Dampers (IBD) Curtain Type or (FD) Multiple Blade Type |
Return to top |
Product Models |
Walls |
Floors |
One-Side Angle Installation |
"Out of
Wall/Floor" |
Grille Access in Shafts |
Round Duct |
Fire Stop
(no angles)
Installation |
"Tunnel" Corridor
Ceilings |
Roof/Floor
Ceiling
Assemblies |
Smoke Detector |
IBD2 / 1.5hr / No Sleeve |
120x72 |
90x91 |
90x48 or 48x90 |
|
|
85 |
90x48 |
|
|
|
IBD23 / 3 hr / No sleeve |
90x72 |
90x91 |
|
|
|
85 |
90x48 |
|
|
|
IBD20, 40, 60 / 1.5hr / Integral Sleeve |
84x72 |
84x84 |
84x48 or 48x84 |
|
|
31 |
84x48 |
|
|
|
IBD230, 430, 630 / 3hr / Integral Sleeve |
84x72 |
84x84 |
|
|
|
31 |
84x48 |
|
|
|
IBDT / 1.5hr / Thinline / No cleeve |
40x48 |
60x12 |
40x48 |
|
|
|
40x48 |
|
|
|
IBD2GA / 1.5 hr / Grille Access |
|
|
|
|
36x36 |
|
|
|
|
|
IBD2OW / 1.5 hr / Out of Wall/Floor |
|
|
|
36x36 |
|
34 |
|
|
|
|
FD35 / 1.5hr / 3V Blades / No sleeve |
120x96 |
120x96 |
90x48 or 48x90 |
|
|
|
90x48 |
|
|
|
FD60 / 1.5hr / AirFoil Blades / No sleeve |
120x96 |
120x96 |
90x48 or 48x90 |
|
|
|
90x48 |
|
|
|
FD60-3 / 3hr / Airfoil Blades |
120x96 |
120x96 |
|
|
|
|
|
|
|
|
FD35SS / 1.5hr. / 3VBlades / No Sleeve |
90x48 |
90x48 |
|
|
|
|
90x48 |
|
|
|
FD60OW / 1.5hr / Out of Wall/Floor |
|
|
|
32x36 |
|
|
|
|
|
|
FD60GA |
|
|
|
32x36 |
|
|
|
|
|
|
FD35GA / 1.5hr / Grille Access |
|
|
|
32x36 |
|
|
|
|
|
|
UL555 Dynamic "Fans On" Fire Dampers (DIBD) Curtain Type or (DFD) Multiple Blade Type |
Return to top |
Product Models |
Walls |
Floors |
One-Side Angle Installation |
"Out of
Wall/Floor" |
Grille Access in Shafts |
Round Duct |
Fire Stop
(no angles)
Installation |
"Tunnel"Corridor
Ceilings |
Roof/Floor
Ceiling
Assemblies |
Smoke Detector |
DIBD2 / 1.5 hr / No Sleeve |
72x48, 48x72 or 120x24 |
36x48 |
72x48 or 48x72 |
|
|
34 |
72x48 or 48x72 |
|
|
|
DIBD2SS / 1.5hr / No Sleeve |
72x48 |
|
72x48 |
|
|
|
|
|
|
|
DIBD23 / 3 hr / No Sleeve |
72x48 or 48x72 |
36x48 |
|
|
|
31 |
72x48 or 48x72 |
|
|
|
DIBD20, 40, 60 / 1.5 hr / Integral Sleeve |
72x48 or 48x72 |
36x48 |
72x48 or 48x72 |
|
|
31 |
72x48 or 48x72 |
|
|
|
DIBD230, 430, 630 / 3 hr / Integral Sleeve |
72x48 or 48x72 |
36x48 |
|
|
|
31 |
72x48 or 48x72 |
|
|
|
DIBD2GA / 1.5 hr / Grille Access |
|
|
|
|
36x36 |
|
|
|
|
|
DIBD2OW / 1.5 hr / Out of Wall/Floor |
|
|
|
36x36 |
|
|
|
|
|
|
DFD35SS / 1.5hr. / 3VBlades / No Sleeve |
90x48 |
|
90x48 |
|
|
|
90x48 |
|
|
|
DFD35OW / 1.5hr / Out of Wall/Floor |
|
|
|
36x36 |
|
|
|
|
|
|
FDR25 / 1.5hr / "True Round" |
24 |
24 |
24 |
|
|
24 |
|
|
|
|
DFD35 |
72x96 or 126x48 |
72x96 or 126x48 |
90x48 or 48x90 |
|
|
|
90x48 |
|
|
|
DFD60 |
64x96 or 120x48 |
64x96 or 120x48 |
90x48 or 48x90 |
|
|
|
90x48 |
|
|
|
DFD60-3 |
60x96/ 120x48 |
60x96/ 120x48 |
|
|
|
|
|
|
|
|
DFD35SS |
90x48 |
90x48 |
|
|
|
|
|
|
|
|
UL555C Ceiling Fire Dampers |
Return to top |
Product Models |
Walls |
Floors |
One-Side Angle Installation |
"Out of
Wall/Floor" |
Grille Access in Shafts |
Round Duct |
Fire Stop
(no angles)
Installation |
"Tunnel" Corridor
Ceilings |
Roof/Floor
Ceiling
Assemblies |
Smoke Detector |
CFD (R) 2, 3, 4, 5 / Rect or Round |
|
|
|
|
|
20 |
|
|
24x24 |
|
CFD7 / Wood Joist |
|
|
|
|
|
|
|
|
16x12 |
|
CFD7(T) / Wood Truss |
|
|
|
|
|
|
|
|
18x18 |
|
CFDR7T (round)/ Wood Truss |
|
|
|
|
|
|
|
|
18 |
|
CFD (R) 2W, 3W, 4W, 5W / Wood Truss |
|
|
|
|
|
20 |
|
|
24x24 |
|
DFSDR1 / Motorized ceiling damper |
|
|
|
|
|
|
|
|
12 |
|